XTREM DN-F cables are designed to supply power to low voltage appliances like submersible pumps in deep water installations, mining installations as well as many other types of electrical equipment. The nominal voltage up to 1000 V thanks to the high dielectric properties of the insulation material (according to HD 516).
XTREM DN-F cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
UNE 21150
Approvals
CE / RoHS
Construction Products Regulation (CPR)
Eca
Thermal performance
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations) and -35ºC (mobile use)
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Reaction to fire CPR: Eca , according to EN 50575.
Mechanical performance
Minimum bending radius: 3 x cable diameter < 12 mm.
4 x cable diameter > 12 mm.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Excellent.
Grease & mineral oils resistance: Excellent.
Water performance
Water resistance: AD8 Submersion.
Submersible pumps
Deep wells
Drinkable water
Other
Meter by meter marking.
Installation conditions
Open Air.
Applications
Industrial use.
Mobile use.
Robotics.
Windmills
Temporary site installations.
Packaging
Available in rolls of 100 m and drums.
XTREM DN-F cable design
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
Rubber (type EPR)
The standard identification of insulated conductors is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
4 G Brown + Negro + Grey + Yellow/green
5 G Brown + Negro + Grey + Blue + Yellow/green
Outer sheath
Flexible rubber. Black colour.