POWERHARD RV U-1000 R2V cable has been specially designed for low voltage industrial-type connections, urban grids, building installations, etc. It can be buried or installed in a tube as well as outdoors without requiring additional protection. Lastly, the POWERHARD® RV / U-1000 R2V cable can withstand damp conditions including total immersion in water (AD7).
POWERHARD RV U-1000 R2V cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
IEC 60502-1 / UNE 21123-2 / NF C 32-321
Approvals
AENOR / BUREAU VERITAS / NF-USE / CE / RoHS
Construction Product Regulation
Eca
Thermal performance
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Reduced halogen emission. Chlorine <15%.
Reaction to fire CPR:
Eca, according to EN 50575.
Mechanical performance
Minimum bending radius: x5 cable diameter.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Good.
UV Resistant: UNE 211605 and NF-C 32-323.
Water performance
Water resistance: AD7 Immersion.
Other
Meter by meter marking.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
Distribution network.
POWERHARD RV U-1000 R2V cable design
Conductor
Electrolytic copper, class 1 (up to 4 mm2) or class 2 (from 6 mm2) based on EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene (XLPE).
The standard identification of insulated conductors is the following:
1 x Natural
2 x Blue + Brown
3G Blue + Brown + Green/yellow
3x Brown + Black + Grey
4G Brown + Black + Grey + Green/yellow
4x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Green/yellow
Outer sheath
Flexible PVC, black colour.