Electrical performance
LOW VOLTAGE 450/750V
Standard
EN 50525-3-41
Approvals
AENOR / HAR / CE / RoHS
CPR Construction Products Regulation
Eca
Thermal performance
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
LSHF (Low Smoke Halogen Free) based on UNE-EN 60754-1 and IEC 60754-1.
Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 60%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Reaction to fire CPR Eca, according to EN 50575.Mechanical performance
Minimum bending radius: x5 cable diameter.
Chemical performance
Chemical & Oil resistance: Acceptable.
Water performance
Water resistance: AD3 Sprays.
Other
Meter by meter marking.
Installation conditions
In conduit.
Applications
Domestic use.
Electric panel wiring.Public places.
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
LSZH Rubber.
The standard identification of insulated conductors is the following:
Blue RAL 5015
Brown RAL 8003
Black RAL 9005
Red RAL 3000
Green/yellow RAL 1021 / RAL 6018
Gray RAL 7000
Other colours available on request.CHEMICAL PERFORMANCE
Chemical & Oil resistance: Acceptable.
FIRE PERFORMANCE
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
ELECTRICAL PERFORMANCE
LOW VOLTAGE 450/750 V
THERMAL PERFORMANCE
Maximum service temperature: 90ºC.
Maximum short-circuit
temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations)
MECHANICAL PERFORMANCE
Minimum bending radius: x5 cable diameter.
WATER PERFORMANCE
Water resistance: AD3 Sprays
APPROVALS
AENOR
CE
HAR
APPLICATIONS
Domestic use.
Electrical panel wiring.
Public places.
CONSTRUCTION PRODUCT REGULATION
Eca
INSTALLATION CONDITIONS
In conduit.
OTHERS
Meter by meter marking.
If you have any questions, please contact us. We’ll do our best to help.